This product is mainly used in large C&I markets, the AC output voltage level will be 690Vac. The cabinet is widely used for various application scenarios such as power distribution, PV system + charging, industrial drilling, mechanical application, etc. It also can meet the requirements of peak shaving, optimization of power factor, applications related to power quality. It also can manage the demand charge, improve power supply reliability and reduce power costs. The cabinet meets the requirements of CE certification.
Share
PRODUCT FEATURES
01
Capable of multiple communication interfaces including RS485/Ethernet/CAN, supporting communication protocols such as Modbus/RTU, Modbus/TCP, IEC104, IEC61850, CAN2.0B, etc.
02
Modular design of core components for easy maintenance.
03
Support PQ/VF/SG operation mode.
04
The integrated 20-ft solution is more suitable for transportation.
05
Support high/low voltage ride-through, zero voltage ride-through, and continuous fault ride-through.
06
IP65 high protection level, C5 anti-corrosion, suitable for various outdoor complex-environment applications.
07
Three-level design, maximum efficiency up to 99%.
08
Fast power dispatch response, PCS power response time <20 ms.
PRODUCT TOPOLOGY
| Model | INPPCS-1250/0.69-OD-OS |
| DC parameters | |
| DC voltage range | 1000-1500V |
| Max.DCcurrent | 1375 A |
| Rated DC power | 1250kW |
| Max. DC power | 1375kW |
| AC parameter (On grid) | |
| Rated power | 1250 kW |
| Max. power | 1375@35°C,1250@50°C kW |
| Rated AC Input current | 1046 A |
| Max. current | 1151A |
| Overload capacity | 1.1times@Long-term 1.2times@lmin |
| Rated voltage | 690 V,3L/PE, IT system |
| AC voltage tolerance | -15% ~+ 10% |
| Rated frequency | 50/60 Hz |
| Power factor Range | -0.99 - +0.99 |
| Harmonic (THDI) | < 3% (at nominal Power), Linear load |
| DC component | ≤0.5% In |
| Access method | 3P3W |
| AC parameter (Off grid) | |
| Rated voltage | 690 V,3 L/PE |
| Rated frequency | 50/60 Hz |
| Rated power | 1250KW |
| Max.power | 1375KW |
| THDU | < 3 % (No load or linear load) |
| Auxiliary power | |
| Nominal AC voltage [V] | 400 V/230 V.380 V/220 V,3 L/N/PE,50/60 Hz |
| Max. Input apparent Power[kVA] | 4.5 |
| Max. Input current [A] | 6.8 |
| System Parameters | |
| On/off grid switching duration | ≤20 ms |
| Ambient temperature | -35°C-+55°C (>50°C derating) |
| Humidity | 0~95 % (No condensation) |
| Altitude | ≤4000 m |
| Protection | IP65 |
| Cooling method | Forced air cooling |
| Dimension | W675*D1876*H2350 mm |
| Weight | ≤1200 kg |
| Interface | RS485/CAN /Ethernet |
Related Products